TECHNISCHE NORMEN
EN 60269-2 section II
PRODUKTVORTEILE
The fuse complies with standard EN 60269-2 section II and standard BS 88 part 2. These fuses are designed for : “General purpose use” motor protection (gM type). This fuse range insures an excellent current limitation for all overloads on a large range of applications. Their size cannot allow exchange by other fuses of higher rating in their range. They are screwed into fuseholders or bolted directly onto busbars, or in fuse interruptors disconnectors.
Weitere SpezifikationenApplications
Teilenummer
S226313
Katalognummer
BTC42V100M200
Description
Britischer Standard-Sicherungseinsatz IEC BS88 gM Typ B1 415VAC 240VDC 100M200A BTC verschraubt
EAN / UPC-Code
3605340267907
Bemessungsbetriebsspannung AC IEC
415 V
Bemessungsbetriebsspannung DC IEC
240 V
In M Ich
100M200 A
Betriebsklasse / Charakteristik
gM
Montageart
Bolted
Ausschalt- I2t bei Bemessungsbetriebsspannung
293000 A²s
Schmelz- I2t
105000 A²s
AC max. Strombelastbarkeit/Ausschaltvermögen: I1
80 kA
Verlustleistung bei Nennstrom
8.1 W
Material der Kontakte
Tin-Plated Copper
Verbindung / Anschluss Typ
Slotted Blades
Produktgewicht
0.24 kg
Produktdurchmesser
31 mm
Produktbreite
0 mm
Produktlänge
136 mm
Verpackungsmenge
5 EACH
Verpackungsgewicht
1.2 kg
Verpackungsbreite
145 mm
Verpackungslänge
180 mm
Verpackungshöhe
40 mm