TECHNISCHE NORMEN
EN 60269-2 section II
PRODUKTVORTEILE
The fuse complies with standard EN 60269-2 section II and standard BS 88 part 2. These fuses are designed for : “General purpose use” motor protection (gM type). This fuse range insures an excellent current limitation for all overloads on a large range of applications. Their size cannot allow exchange by other fuses of higher rating in their range. They are screwed into fuseholders or bolted directly onto busbars, or in fuse interruptors disconnectors.
Weitere SpezifikationenApplications
Teilenummer
L1019209
Katalognummer
BTSDC42V63M100
Description
Britischer Standard-Sicherungseinsatz IEC BS88 gM Typ B1 415VAC 240VDC 63M100A BTSDL verschraubt
EAN / UPC-Code
3605340515985
Bemessungsbetriebsspannung AC IEC
415 V
Bemessungsbetriebsspannung DC IEC
240 V
In M Ich
63M100 A
Betriebsklasse / Charakteristik
gM
Montageart
Bolted
Ausschalt- I2t bei Bemessungsbetriebsspannung
65000 A²s
Schmelz- I2t
14000 A²s
AC max. Strombelastbarkeit/Ausschaltvermögen: I1
80 kA
Verlustleistung bei Nennstrom
4.7 W
Material der Kontakte
Tin-Plated Copper
Verbindung / Anschluss Typ
Slotted Blades
Produktgewicht
0.086 kg
Produktdurchmesser
21 mm
Produktbreite
0 mm
Produktlänge
127 mm
Verpackungsmenge
10 EACH
Verpackungsgewicht
0.86 kg
Verpackungsbreite
135 mm
Verpackungslänge
143 mm
Verpackungshöhe
55 mm