TECHNISCHE NORMEN

  • IEC 60269-1 and IEC 60269-4 Compliance
  • DC UL recognized component
  • UL file E76491
  • - 160A-420A, @1200VDC, L/R 10ms, 100KA
  • - 160A-420A, @1500VDC, L/R 1-3ms, 100KA
  • GB/T 13539.4-2016

PRODUKTVORTEILE

Mersen DC offers provide a very high performant protection for railway power and auxiliary circuits. Mersen DC Semiconductor fuse-links were developed to provide improved performance required by today's new DC equipment. These fuse-links are typically operated at more elevated temperature than other fuse type, have lower I²t to minimize damage to protected components on short circuits, lower watt loss and longer life.

Weitere Spezifikationen

Applications

  • Protection of inverters
  • Protection of motor drives
  • Protection of UPS systems
  • Railway power and auxiliary circuits
  • ESS Battery Rack protection up to 1500VDC

Produktspezifikationen

Teilenummer

P079432  

Katalognummer

D72SG120V400QF  

Artikelbeschreibung (ERP)

CC12 SRG 72 QF 400  

Beschreibung

Size 72 aR 1200VDC(IEC), with striker aR 400 A VAC/1200VDC  

EAN / UPC-Code

3605340033984  

Bemessungsbetriebsspannung DC IEC

1200   V

Bemessungsstrom

400   A

RoHS-Konformität

Ja  

Betriebsklasse / Charakteristik

aR  

Baugröße

72  

Montageart

Bolted  

Ausschalt- I2t bei Bemessungsbetriebsspannung

182   kA²s

Verlustleistung bei Nennstrom

129   W

Designdetails

SRG  

Anzeigesystem

Ja  

Anzeigesystemtyp

Striker  

Material des (Sicherungs-) Körpers

Ceramic  

Produktgewicht

1.15   kg

Produktbreite

60   mm

Produktlänge

163   mm

Produkthöhe

76.5   mm

Verpackungsmenge

1   EACH

Verpackungsgewicht

1.15   kg

Verpackungsbreite

130   mm

Verpackungslänge

200   mm

Verpackungshöhe

95   mm