TECHNISCHE NORMEN
EN 60269-2 section II
PRODUKTVORTEILE
The fuse complies with standard EN 60269-2 section II and standard BS 88 part 2. These fuses are designed for : “General purpose use” protection (gG type). This fuse range insures an excellent current limitation for all overloads on a large range of applications. Their size cannot allow exchange by other fuses of higher rating in their range. They are screwed into fuseholders or bolted directly onto busbars, or in fuse interruptors disconnectors.
Weitere SpezifikationenApplications
Teilenummer
N226332
Katalognummer
BTLM42V670
Description
Britischer Standard-Sicherungseinsatz IEC BS88 gG Typ C3 415VAC 240VDC 670A BTLM verschraubt
EAN / UPC-Code
3605340268096
Bemessungsbetriebsspannung AC IEC
415 V
Bemessungsbetriebsspannung DC IEC
240 V
Bemessungsstrom
670 A
Betriebsklasse / Charakteristik
gG
Montageart
Bolted
Ausschalt- I2t bei Bemessungsbetriebsspannung
5460000 A²s
Schmelz- I2t
1950000 A²s
AC max. Strombelastbarkeit/Ausschaltvermögen: I1
80 kA
Verlustleistung bei Nennstrom
60 W
Material der Kontakte
Tin-Plated Copper
Verbindung / Anschluss Typ
Slotted Blades
Produktgewicht
1.36 kg
Produktdurchmesser
82.4 mm
Produktbreite
0 mm
Produktlänge
212 mm
Verpackungsmenge
1 EACH
Verpackungsgewicht
1.36 kg
Verpackungsbreite
75 mm
Verpackungslänge
235 mm
Verpackungshöhe
75 mm