TECHNISCHE NORMEN
PRODUKTVORTEILE
Mersen’s GEN2 of the HP15M photovoltaic (PV) fuse series is designed specifically to meet the severe temperature and current cycling of a PV system. Subjected to stringent cycle testing, the GEN2 provides enhanced reliability. These 1500VDC rated fuses are designed for low minimum breaking capacity capabilities of 1.35 times the fuse rated current value, which allows for safe circuit interruption under typical low fault current conditions. In addition to the standard ferrule terminal, parts are also available with Crimp Cap terminals for in-line fuse applications. The unique wire crimp terminal (CC option) permits solderless wire-to-fuse connection for overmold encapsulation of fuse and wiring. Protect your off-grid or grid tied PV system from unexpected line faults using Mersen’s HelioProtection® fuse line.
Weitere SpezifikationenApplications
Dokumente & Ressourcen
Datenblatt
Zeichnungen
Curves
Teilenummer
HP15M4RCC
Description
Photovoltaik-Sicherung gPV 1500VDC IEC 1500VDC UL Größe 10x85 4A mit Crimp Cap Für Crimp
EAN / UPC-Code
782001504434
Bemessungsbetriebsspannung DC UL
1500 V
Bemessungsbetriebsspannung DC IEC
1500 V
Bemessungsstrom
4 A
RoHS-Konformität
Ja
Wechselstrom oder Gleichstrom
DC
Sicherungs Betriebsklasse
PV
Betriebsklasse / Charakteristik
gPV
Baugröße
10x85
Montageart
Crimp
AC max. Strombelastbarkeit/Ausschaltvermögen: I1
50 kA
Verlustleistung bei Nennstrom
1.69 W
Leistungsdissipation bei Zwischenstromwert
0.80 @ 0.7 In W
Material der Kontakte
Kupfer mit Zinnbeschichtung
Verbindung / Anschluss Typ
Crimp Cap
Material des (Sicherungs-) Körpers
GMG
Produktgewicht
0.0181 kg
Produktdurchmesser
11.4 mm
Produktlänge
112 mm
Verpackungsmenge
5 EA
Verpackungsgewicht
0.0907 kg
Verpackungsbreite
14.2 mm
Verpackungslänge
60.5 mm
Verpackungshöhe
114.3 mm