TECHNISCHE NORMEN
PRODUKTVORTEILE
Amp-Trap 2000® time-delay A6D-R fuses provide IEC Type 2 "no damage" protection to existing mains, feeders, and branch circuits serving motor and non-motor loads. A6D-R fuses will open fast enough under extreme fault conditions for maximum short circuit protection to prevent damage to motor starters, switches, and other circuit components, yet also provide the time-delay needed for motor in-rush currents. A6D-R fuses can be used to replace older 600V Class H, K or RK5 fuses already installed in the field.
Weitere SpezifikationenApplications
Dokumente & Ressourcen
Datenblatt
Zeichnungen
Curves
Compliance
Teilenummer
A6D60R
Description
Sicherungseinsatz A6D-R - Class RK1 - Time-Delay 600VAC 600VDC 60A Kapselsicherung SmartSpot® Amp-Trap 2000®
EAN / UPC-Code
782001992040
Bemessungsbetriebsspannung AC UL
600 V
Bemessungsbetriebsspannung DC UL
600 V
Frequenz
50/60 Hz
Bemessungsstrom
60 A
Wechselstrom oder Gleichstrom
AC/DC
Sicherungs Betriebsklasse
Klasse RK1
Betriebsklasse / Charakteristik
Time Delay
Montageart
Klemme
AC max. Strombelastbarkeit/Ausschaltvermögen: I1
200 kA
Anzeigesystem
Ja
Anzeigesystemtyp
SmartSpot®
Material der Kontakte
Kupfer mit Zinnbeschichtung
Verbindung / Anschluss Typ
Keramiksicherung
Material des (Sicherungs-) Körpers
PolyTube
Produktgewicht
0.1542 kg
Produktdurchmesser
26.9 mm
Produktlänge
139.7 mm
Verpackungsmenge
10 EA
Verpackungsgewicht
1.6193 kg
Verpackungsbreite
55.6 mm
Verpackungslänge
139.7 mm
Verpackungshöhe
142.7 mm