TECHNISCHE NORMEN
A4BQ (100-6000)
PRODUKTVORTEILE
Amp-Trap 2000 A4BQ fuses are 20 percent more current limiting than any other Class L fuse on the market. When correctly coordinated, they bring a superior level of protection to service entrance equipment. Downstream circuit components have maximum protection against short circuit let-thru current. A4BQ's built-in 4-second time-delay characteristic (at 500percent of rated current) accommodates harmless inrush currents with no nuisance opening.
Weitere SpezifikationenApplications
Dokumente & Ressourcen
Datenblatt
Zeichnungen
Curves
Teilenummer
A4BQ5000-TA
Description
Sicherungseinsatz A4BQ – Klasse L – träge 600VAC 5000A Kontaktmesser TA-Indikator Amp-Trap 2000®
EAN / UPC-Code
782001294175
Bemessungsbetriebsspannung AC UL
600 V
Bemessungsstrom
5000 A
RoHS-Konformität
Ja
Sicherungs Betriebsklasse
Class L
Betriebsklasse / Charakteristik
Time Delay
Montageart
Bolted
AC max. Strombelastbarkeit/Ausschaltvermögen: I1
200 kA
Anzeigesystem
Ja
Anzeigesystemtyp
TA Indicator
Material der Kontakte
Silver-Plated Copper
Verbindung / Anschluss Typ
Blade
Material des (Sicherungs-) Körpers
GMG
Produktgewicht
14.3789 kg
Produktdurchmesser
158.8 mm
Produktlänge
273 mm
Verpackungsmenge
1 Each
Verpackungsgewicht
15.1001 kg
Verpackungsbreite
165.1 mm
Verpackungslänge
296.7 mm
Verpackungshöhe
171.4 mm