TECHNISCHE NORMEN
PRODUKTVORTEILE
Amp-Trap 2000 time-delay A2D-R fuses provide IEC Type 2 "no damage" protection to existing mains, feeders, and branch circuits serving motor and non-motor loads. A2D-R fuses will open fast enough under extreme fault conditions for maximum short circuit protection to prevent damage to motor starters, switches, and other circuit components, yet also provide the time-delay needed for motor in-rush currents. A2D-R fuses can be used to replace older 250V Class H, K or RK5 fuses already installed in the field.
Weitere SpezifikationenApplications
Dokumente & Ressourcen
Datenblatt
Zeichnungen
Compliance
Teilenummer
A2D450RN
Description
Sicherungseinsatz A2D-R - Class RK1 - Time-Delay 250VAC 250VDC 450A Kontaktmesser Amp-Trap 2000®
EAN / UPC-Code
782001504595
Bemessungsbetriebsspannung AC UL
250 V
Bemessungsbetriebsspannung DC UL
250 V
Frequenz
50/60 Hz
Bemessungsstrom
450 A
RoHS-Konformität
Ja
Wechselstrom oder Gleichstrom
AC/DC
Sicherungs Betriebsklasse
Klasse RK1
Betriebsklasse / Charakteristik
Time Delay
Montageart
Klemme
AC max. Strombelastbarkeit/Ausschaltvermögen: I1
200 kA
Anzeigesystem
Ja
Anzeigesystemtyp
SmartSpot®
Material der Kontakte
Kupfer mit Zinnbeschichtung
Verbindung / Anschluss Typ
Kontaktmesser
Material des (Sicherungs-) Körpers
PolyTube
Produktgewicht
1.3304 kg
Produktdurchmesser
79.4 mm
Produktlänge
263.7 mm
Verpackungsmenge
1 EA
Verpackungsgewicht
1.3971 kg
Verpackungsbreite
66.5 mm
Verpackungslänge
66.5 mm
Verpackungshöhe
274.6 mm