Approvals & Standards

EN 60269-2 section II

Key features & benefits

The fuse complies with standard EN 60269-2 section II and standard BS 88 part 2. These fuses are designed for : “General purpose use” motor protection (gM type). This fuse range insures an excellent current limitation for all overloads on a large range of applications. Their size cannot allow exchange by other fuses of higher rating in their range. They are screwed into fuseholders or bolted directly onto busbars, or in fuse interruptors disconnectors.

More specifications

Applications

  • These fuses are designed for : “General purpose use” motor protection (gM type)

Product Specifications

Item Number

R226312  

Catalog number

BTC42V100M160  

Description

British Standard fuse-link IEC BS88 gM Type B1 415VAC 240VDC 100M160A BTC Central Bolted Tag  

EAN/UPC code

3605340519976  

Rated voltage AC IEC

415   V

Rated voltage DC IEC

240   V

In M Ich

100M160   A

Speed/Characteristic

gM  

Mounting

Bolted  

Clearing I2t At Rated Voltage

168000   A²s

Melting I2t

60000   A²s

AC Max I.R./Breaking Capacity: I1

80   kA

Power Dissipation at Rated Current Value

8.8   W

Contact materials

Tin-Plated Copper  

Connection/Terminal Type

Slotted Blades  

Product Weight

0.12   kg

Product Diameter

31   mm

Product Width

0   mm

Product Length

136   mm

Sell Pack Quantity

10   EACH

Sell Pack Weight

1.2   kg

Sell Pack Width

145   mm

Sell Pack Length

195   mm

Sell Pack Height

70   mm