Approvals & Standards
EN 60269-2 section II
Key features & benefits
The fuse complies with standard EN 60269-2 section II and standard BS 88 part 2. These fuses are designed for : “General purpose use” motor protection (gM type). This fuse range insures an excellent current limitation for all overloads on a large range of applications. Their size cannot allow exchange by other fuses of higher rating in their range. They are screwed into fuseholders or bolted directly onto busbars, or in fuse interruptors disconnectors.
More specificationsApplications
Documents & Resources
Datasheet
Compliance
Item Number
Q226311
Catalog number
BTC42V100M125
Description
British Standard fuse-link IEC BS88 gM Type B1 415VAC 240VDC 100M125A BTC Central Bolted Tag
EAN/UPC code
3605340519969
Rated voltage AC IEC
415 V
Rated voltage DC IEC
240 V
In M Ich
100M125 A
ROHS Compliant
Yes
AC or DC
AC/DC
Speed/Characteristic
gM
Fuse size
B1
Mounting
Bolted
Clearing I2t At Rated Voltage
78400 A²s
Melting I2t
28000 A²s
Max. Rated Breaking Capacity DC
40 kA
AC Max I.R./Breaking Capacity: I1
80 kA
Power Dissipation at Rated Current Value
9 W
Contact materials
Tin-Plated Copper
Connection/Terminal Type
Central Bolted Tag
Body/Insulating Material
Ceramic
Comments
BTC
Product Weight
0.12 kg
Product Diameter
31 mm
Product Width
0 mm
Product Length
136 mm
Sell Pack Quantity
10 EA
Sell Pack Weight
1.2 kg
Sell Pack Width
145 mm
Sell Pack Length
195 mm
Sell Pack Height
70 mm