Approvals & Standards
Key features & benefits
Mersen’s fusible disconnect switches are listed to UL 98 and bear the CE mark conforming to IEC 60947-3. They are “service entrance” devices capable of fully rated load-break and load-make. While longterm safety, reliability, and functionality are always paramount in the design of our products, these switches are also engineered to have the smallest footprint. The modular design allows placement of the handle anywhere amongst the poles. The fuse doors cannot open when the switch is in the “ON” position, and all switches are double-break, which isolates both fuse clips from voltage during fuse replacement. The switches’ “Test” position allows actuation of the auxiliary contacts without main power. Power taps enable energizing a CPT or surge device without the need for a separate terminal block. A wide range of ergonomic handles and accessories is available.
Applications
Item Number
M1200L40
Description
UL 98 Fusible Switch 600VAC Class L 1200A 4-Pole Configuration: 4-0
EAN/UPC code
3605340561289
Rated voltage AC UL
600 V
Rated voltage DC UL
250 V
Rated current
1200 A
ROHS Compliant
Yes
AC or DC
AC/DC
Short Circuit Current Rating (SCCR)
200 kA
Short Circuit Rating (Standalone)
200 kA
Fuse Type/Class
Class L
Number of Poles
4-Pole
Contact materials
Silver-Plated Copper
Connection/Terminal Type
Blade
Max Fuse Rated Current
1200 A
Max Horsepower Rating/FLA
3-Phase: 240V 250HP, 480V 500HP, 600V 500HP
Contact type
Double Break
Rated Insulation Voltage
1000 V
Installation Mounting
Direct Screw Mount
Comments
4-0
Product Weight
53.8868 kg
Product Width
539 mm
Product Length
426 mm
Product Height
293.9 mm
Sell Pack Quantity
1 EA
Sell Pack Weight
56.5811 kg
Sell Pack Width
640.6 mm
Sell Pack Length
527.6 mm
Sell Pack Height
395.5 mm