Skip to main content

All locations

Please select your country & language

China | 中国
Germany | Deutschland

Your country is not in the list?

Go to our international website:

Mersen EP International website
Contact us

Approvals & Standards

EN 60269-2 section II

Key features & benefits

The fuse complies with standard EN 60269-2 section II and standard BS 88 part 2. These fuses are designed for : “General purpose use” motor protection (gM type). This fuse range insures an excellent current limitation for all overloads on a large range of applications. Their size cannot allow exchange by other fuses of higher rating in their range. They are screwed into fuseholders or bolted directly onto busbars, or in fuse interruptors disconnectors.

More specifications

Applications

  • These fuses are designed for : “General purpose use” motor protection (gM type)

Product Specifications

Item Number

K1019277  

Catalog number

BTCP69V32M36  

Description

British Standard fuse-link IEC BS88 gM Type A4 690VAC 460VDC 32M36A BTCP Offset Tag  

EAN/UPC code

3605340515961  

Rated voltage AC IEC

690   V

Rated voltage DC IEC

460   V

In M Ich

32M36   A

ROHS Compliant

Yes  

AC or DC

AC/DC  

Speed/Characteristic

gM  

Fuse size

A4  

Mounting

Bolted  

Clearing I2t At Rated Voltage

4500   A²s

Melting I2t

700   A²s

Max. Rated Breaking Capacity DC

40 kA  

AC Max I.R./Breaking Capacity: I1

80   kA

Power Dissipation at Rated Current Value

3.4   W

Contact materials

Tin-Plated Copper  

Connection/Terminal Type

Offset Tag  

Body/Insulating Material

Ceramic  

Comments

BTCP  

Product Weight

0.082   kg

Product Diameter

21   mm

Product Width

22.3   mm

Product Length

109   mm

Sell Pack Quantity

5   EA

Sell Pack Weight

0.41   kg

Sell Pack Width

117   mm

Sell Pack Length

218   mm

Sell Pack Height

38   mm