Direkt zum Inhalt

All locations

Please select your country & language

China | 中国
Germany | Deutschland

Your country is not in the list?

Go to our international website:

Mersen EP International Website
Kontakt

TECHNISCHE NORMEN

  • Some UL Listed to standard File E143362

PRODUKTVORTEILE

Mersen Amp-Trap fuses for the protection of transformers and distribution lines deliver overload and short circuit protection. These general purpose current-limiting fuses will melt at current that can be as low as 1.7 times the fuse current ratings up to its maximum interrupting rating. These fuses are designed to withstand the transformer magnetizing inrush current. They are single, double or triple barrels 3 inch diameter (size D) and mount in unique cam-locking clips for superior connections as well as easy installation and replacement.

Weitere Spezifikationen

Applications

  • Protection for 5.5kV to 15.5kV transformers or distribution systems

Produktspezifikationen

Frequenz (Hz)

50/60   Hz

Bemessungsstrom

60E and 200E  

Betriebsklasse / Charakteristik

E-Rated  

UL Dateinummer

File E143362  

UL-Kategoriecode

JEEG  

REACH Konformität

Ja  

Max Betriebstemperatur

80   °C

Max. Lagertemp.

80   °C

Min. Lagertemp.

-25   °C

harmonisiertes System

853510  

Referenzen in dieser Serie  (2)

Anzeigesystem

A083C1D0R0-60E

60   A

-

-

Ja  

5.4431   kg

A083C2D0R0-200E

200   A

-

-

Ja  

9.979   kg