TECHNISCHE NORMEN
EN 60269-2 section II
PRODUKTVORTEILE
The fuse complies with standard EN 60269-2 section II and standard BS 88 part 2. These fuses are designed for : “General purpose use” protection (gG type). This fuse range insures an excellent current limitation for all overloads on a large range of applications. Their size cannot allow exchange by other fuses of higher rating in their range. They are screwed into fuseholders or bolted directly onto busbars, or in fuse interruptors disconnectors.
Weitere SpezifikationenApplications
Documents & Resources
Compliance
Teilenummer
F1019273
Katalognummer
BTLM69V750
Artikelbeschreibung (ERP)
BTLM69V750 C3
Description
Central Bolted Tag fuse-links gG BTLM 690VAC 69V750 A
EAN / UPC-Code
3605340515763
Nennspannung AC IEC
690 V
In M Ich
69V750 A
Betriebsklasse / Charakteristik
gG
Montage
Bolted
Clearing I2t At Rated Voltage
14200 kA²s
Schmelzen I2t
3000 kA²s
AC Max I.R./Breaking Capacity: I1
80 kA
Power Dissipation at Rated Current Value
65 W
Material der Kontakte
Tin-Plated Copper
Verbindung / Anschluss Type
Slotted Blades
Produktgewicht
1.4 kg
Produktdurchmesser
82.4 mm
Produktbreite
0 mm
Produktlänge
212 mm
Packmenge verkaufen
1 EACH
Packgewicht verkaufen
1.4 kg
Packbreite verkaufen
90 mm
Packlänge verkaufen
210 mm
Packhöhe verkaufen
85 mm