PRODUKTVORTEILE
Extremely high breaking capacity fuses:
Protection of power semiconductors as per IEC standard 60269-1 and -4
690V voltage rating as per IEC 33
gR class (current ratings 12 to 90A) as per VDE 636-23
- Clearing all overloads
- Improved safety and protection
- Enabling selective coordination with all fuses within distribution circuit
aR class (current ratings 100A) according to VDE 636-23 and IEC 60269-4
Connection as per:
- German standard DIN 43653/00C
- British standard BS88-4
These fuses are UL Recognized
Teilenummer
C099960
Katalognummer
BS217UT69V150
Description
Sicherungseinsatz nach britischem Standard Protistor® 2x17x49 gR 690V AC UL 150A
EAN / UPC-Code
3605340164039
Bemessungsbetriebsspannung AC UL
1
Bemessungsstrom
150 A
Baugröße
2x17x49
Montageart
Bolted
Ausschalt- I2t bei Bemessungsbetriebsspannung
18500 A²s
Schmelz- I2t
2090 A²s
AC max. Strombelastbarkeit/Ausschaltvermögen: I1
200 kA
Verlustleistung bei Nennstrom
28.7 W
Material des (Sicherungs-) Körpers
Ceramic
Produktgewicht
0.0828 kg
Produktdurchmesser
0 mm
Produktbreite
36.7 mm
Produktlänge
90.2 mm
Produkthöhe
18.5 mm
Verpackungsmenge
5 EACH
Verpackungsgewicht
0.414 kg
Verpackungsbreite
103 mm
Verpackungslänge
195 mm
Verpackungshöhe
24 mm