TECHNISCHE NORMEN
PRODUKTVORTEILE
Mersen R-Rated fuses are current-limiting, high interrupting rating fuses intended for the short circuit protection of medium voltage motors and motor controllers. R-Rated fuses are back-up fuses that have a minimum interrupting rating, and must be coordinated with overload relays in combination motor starters. The motor starter manufacturer generally specifies the R-Rated fuse size. These fuses are single, double, triple or quadruple barrels 3 inches diameter with end mounts designed for bolting directly to equipment bus or terminal pads.
Weitere SpezifikationenApplications
Dokumente & Ressourcen
Datenblatt
Zeichnungen
Curves
Compliance
Teilenummer
A051B3DAR0-48X
Description
Backup-Mittelspannungssicherung mit R-Rating 5080VAC 48X Montage: geschraubt Stil: DAR0 mit Kennmelder Amp-Trap®
EAN / UPC-Code
782001804343
Bemessungsbetriebsspannung AC UL
5080 V
Frequenz
50/60 Hz
Betriebsklasse / Charakteristik
R-Rated
Montageart
Bolted
AC max. Strombelastbarkeit/Ausschaltvermögen: I1
50 kA
Mindestunterbrechungsrate (MBC)
50 kA
Anzeigesystem
Ja
Anzeigesystemtyp
Visual Indicator
Material der Kontakte
Silver-Plated Copper
Verbindung / Anschluss Typ
Bolted
Material des (Sicherungs-) Körpers
GMG
Produktgewicht
14.9685 kg
Produktbreite
76.2 mm
Produktlänge
489 mm
Produkthöhe
295.4 mm
Verpackungsmenge
1 Each
Verpackungsgewicht
15.717 kg
Verpackungsbreite
311.2 mm
Verpackungslänge
527 mm
Verpackungshöhe
85.9 mm